![Siemens SINAMICS G120P Скачать руководство пользователя страница 410](http://html.mh-extra.com/html/siemens/sinamics-g120p/sinamics-g120p_operating-instructions-manual_378189410.webp)
Functions
7.7 Application-specific functions
Inverter cabinet units
410
Operating Instructions, 12/2014, A5E32923362A
Table 7- 35 Order of deactivation for external motors depending on setting in p2371
p2371
Activated motors
Stage 1
Stage 2
Stage 3
Stage 4
Stage 5
Stage 6
1
M1
M1
2
M1+M2
M1+M2
M1
3
M1+M2
M1+M2
M2
M1
4
M1+M2+M3
M1+M2+M3
M1+M2 M1
5
M1+M2+M3
M1+M2+M3
M3+M1 M3
M1
6
M1+M2+M3
M1+M2+M3
M3+M2 M2+M1
M2
M1
7
M1+M2+M3
M1+M2+M3
M3+M1 M3
M2+M1
M1
8
M1+M2+M3
M1+M2+M3
M3+M2 M3+M1
M3
M2
M1
If you are using motors of the same power rating, you can use p2372 to define whether the
motors are to be activated/deactivated following the setting specified in p2371 (p2372 = 0) or
based on the operating hours (p2372 = 1, 2 ,3. Details see parameter list).