Operation
6.8 Communication via RS485
Inverter cabinet units
238
Operating Instructions, 12/2014, A5E32923362A
The response returns the corresponding data set:
Table 6- 24 Slave response to the read request
Example
Byte
Description
11 h
03 h
04 h
11 h
22 h
33 h
44 h
xx h
xx h
0
1
2
3
4
5
6
7
8
Slave address
Function code
Number of bytes (4 bytes are returned)
Data of first register "High"
Data of first register "Low"
Data of second register "High"
Data of second register "Low"
CRC "Low"
CRC "High"
Structure of a write request via Modbus function code 06 (FC 06)
Start address is the holding register address.
Using FC 06, precisely one register can always be addressed with one request. The value to
be written to the addressed register is contained in bytes 4 and 5 of the write request.
Table 6- 25 Write request and response of the inverter
Write request
Inverter response
Incorrect address (a holding register address does not exist) Exception code 02
Write to a "read-only" register
Modbus error telegram (exception code 04 - device failure)
Write to a reserved register
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......