Operation
6.9 Communication over CANopen
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
265
SDO abort codes
Abort code
Description
0503 0000 hex
Toggle bit not alternated.
0504 0000 hex
SDO protocol timed out.
0504 0001 hex
Client/server command specifier not valid or unknown.
0504 0002 hex
Invalid block size (block mode only).
0504 0003 hex
Invalid sequence number (block mode only).
0504 0004 hex
CRC error (block mode only).
0504 0005 hex
Out of memory.
0601 0000 hex
Unsupported access to an object.
0601 0001 hex
Attempt to read a write only object.
0601 0002 hex
Attempt to write a read only object.
0602 0000 hex
Object does not exist in the object dictionary.
0604 0041 hex
Object cannot be mapped to the PDO.
0604 0042 hex
The number and length of the objects to be mapped would exceed PDO length.
0604 0043 hex
General parameter incompatibility reason.
0604 0047 hex
General internal incompatibility in the device.
0606 0000 hex
Access failed due to an hardware error.
0607 0010 hex
Data type does not match, length of service parameter does not match.
0607 0012 hex
Data type does not match, length of service parameter too high.
0607 0013 hex
Data type does not match, length of service parameter too low.
0609 0011 hex
Subindex does not exist.
0609 0030 hex
Value range of parameter exceeded (only for write access).
0609 0031 hex
Value of parameter written too high.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......