Technical specifications
11.3 Technical specifications
Inverter cabinet units
478
Operating Instructions, 12/2014, A5E32923362A
Article number
6SL3710- 1PE32-1AA0
1PE32-5AA0
1PE33-0AA0
Motor cable length, max.
- compliant with categories C2 and C3
according to EN 61800-3, shielded
m
100
100
100
- non-compliant with the limit values for
interference and without output choke
or dv/dt filter, unshielded
m
200
200
200
- non-compliant with the limit values for
interference and with output choke or
dv/dt filter, shielded/unshielded
m
300/450
300/450
300/450
Dimensions (standard version)
- Width
- Height
8)
- Depth
mm
mm
mm
1000
2000
600
1000
2000
600
1000
2000
600
Power Module frame size
GX
GX
GX
Weight (without options), approx.
kg
360
360
370
Recommended protection
- Line protection
(with option L26)
Rated current
frame size to IEC 60269
- Line and semiconductor protection
(without option L26)
Rated current
Frame size to IEC 60269
A
A
3NA3144
250
1
3NE1230-2
315
1
3NA3252
315
2
3NE1331-2
350
2
3NA3260
400
2
3NE1333-2
450
2
Short-circuit current rating according to
IEC
9)
kA
65
65
65
Minimum short-circuit current
10)
- For 3NE1 fuses
- For 3NA3 fuses
A
A
3000
5800
3600
7300
4400
9500
1)
Rated output of a typical 4-pole standard induction motor based on I
L
or I
H
at 3-phase 400 V AC 50 Hz.
2)
Rated output of a typical 4-pole standard induction motor based on I
L
or I
H
at 3-phase 460 V AC 60 Hz.
3)
The base-load current I
L
is based on a duty cycle of 110% for 60 s or 135% for 3 s with a duty cycle duration of 300 s (see
"Overload capability").
4)
The base-load current I
H
is based on a duty cycle of 150% for 60 s with a duty cycle duration of 300 s (see "Overload
capability").
5)
The current values given here are based on the rated output current.
6)
The recommendations for the North American market in AWG or MCM must be taken from the appropriate NEC (National
Electrical Code) or CEC (Canadian Electrical Code) standards.
7)
The connecting blocks can be damaged when using longer screws.
8)
The cabinet height increases by 300 mm for IP20 and IP21 degrees of protection, and by 400 mm for IP23, IP43 and IP54
degrees of protection.
9)
In conjunction with the specified fuses or circuit breakers.
10)
Minimum current required for reliable activation of the designated protection devices.
Caution: If the minimum short circuit current is not reached, the rupture time of the fuses is increased, which can lead to
damage.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......