Functions
7.7 Application-specific functions
Inverter cabinet units
392
Operating Instructions, 12/2014, A5E32923362A
Simplified representation of the technology controller
The technology controller is implemented as PID controller (controller with proportional,
integral and differential component) which means that it can be very flexibly adapted.
Figure 7-23 Simplified representation of the technology controller
①
The inverter uses the start value when all the following conditions are satisfied:
●
The technology controller supplies the main setpoint (p2251 = 0).
●
The ramp-function generator output of the technology controller has not yet reached the
start value.
For more information, refer to the parameter descriptions and the function block diagrams
7950 - 7958 of the List Manual.
Optimizing a closed-loop controller
You optimize the technology controller as described in Section Optimizing the closed-loop
speed controller (Page 358).