![Siemens SINAMICS G120P Скачать руководство пользователя страница 108](http://html.mh-extra.com/html/siemens/sinamics-g120p/sinamics-g120p_operating-instructions-manual_378189108.webp)
Electrical installation
4.9 Other connections
Inverter cabinet units
108
Operating Instructions, 12/2014, A5E32923362A
4.9.4
dv/dt filter plus Voltage Peak Limiter (option L10)
Description
The dv/dt filter plus Voltage Peak Limiter comprises two components: the dv/dt reactor and
the Voltage Peak Limiter, which cuts off the voltage peaks and returns the energy to the DC
link.
The dv/dt filters plus Voltage Peak Limiter must be used for motors for which the proof
voltage of the insulation system is unknown or insufficient.
The dv/dt filter plus Voltage Peak Limiter limits the voltage gradient to values < 500 V/µs and
the typical transients to the values below (with motor cable lengths of < 150 m):
●
< 1000 V at V
line
< 575 V
An additional cabinet with a width of 400 mm is necessary for the following cabinet drives
with option L10 (this increases the weight to approx. 300 kg):
●
6SL3710-1PE35-8AA0
●
6SL3710-1PE36-6AA0
●
6SL3710-1PE37-4AA0
Restrictions
The following restrictions should be observed when a dv/dt filter plus Voltage Peak Limiter is
used:
●
Maximum permissible motor cable lengths:
–
Shielded cable: max. 300 m
–
Unshielded cable: max. 450 m
NOTICE
Material damage due to component failure for operation of the dv/dt filter without connected
motor
When a dv/dt filter plus Voltage Peak Limiter is used, the drive must not be operated
without a connected motor, otherwise the filter could be destroyed because of component
failure.
•
Never operate the dv/dt filter plus Voltage Peak Limiter without a connected motor.
NOTICE
Damage to the dv/dt filter due to lack of activation during commissioning
Not activating the dv/dt filter plus Voltage Peak Limiter during commissioning can lead to
damage to the dv/dt filter.
•
Activate the dv/dt filter compact plus Voltage Peak Limiter during commissioning with
the parameter p0230 = 2.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......