Operation
6.6 PROFIenergy profile for PROFINET
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
205
PROFIenergy status requests
●
List_Energy_Saving_Modes
Determines all supported energy-saving modes.
●
GeLMode
Determines information about the selected energy-saving mode.
●
PEM_Status
Determines the current PROFienergy status.
●
PEM_Status_with_CTTO
Determines the current PROFienergy status, such as the PEMStatus, together with the
regular transition time to the operating state.
●
PEldentify
Determines the supported PROFienergy commands.
●
Query Version
Shows the implemented PROFienergy profile.
●
Get_Measurement_List
This command returns the measured value IDs that can be accessed using the
"Get_Measurement_Values" command.
●
Get_Measurement_List_with_object_number
This command returns the measured value IDs and the associated object number that
can be accessed using the "Get_Measurement_Values_with_object_number" command.
●
Get_Measurement_ Values
The command returns the requested measured value using the measured value ID.
●
Get_Measurement_Values_with_object_number
The command returns the requested measured values using the measured value ID and
the object number. The object number corresponds to the drive object ID.
Displaying
●
r5600: Current energy-saving mode
●
r5613: Interconnectable display of the PROFIenergy state
●
A08800: PROFIenergy energy-saving mode active
General settings for PROFIenergy
●
Minimum pause time: p5602
The inverter enters energy-saving mode only when the pause time sent with the
"Start_Pause" command is greater than or equal to the value for p5602.1. If the pause
time is less than p5602.1, the inverter ignores the command.
●
Maximum pause time: p5606
Block PROFIenergy control commands
If you set p5611.0 = 1, you block the response of the inverter to PROFIenergy control
commands. In this case, the inverter ignores the PROFIenergy control commands.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......