Commissioning
5.5 Procedure for commissioning via STARTER
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
163
Note
Motors connected in parallel
When connecting motors in parallel, observe the notes in parameter p0306 in the List
Manual.
⇒
Click on Continue >
Configuring the motor – entering motor data
Figure 5-24 Configuring the motor – entering motor data
⇒
Enter the motor data (see motor rating plate).
⇒
Select under Motor connection type: whether the motor is connected in the star- or delta
connection.
⇒
If the motor has a delta connection, you can select in 87Hz calculation that the motor is
operated with 87 Hz.
⇒
Click on Continue >