Technical specifications
11.2 General data
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
473
11.2.1.3
Derating factor of the output current as a function of the line voltage
Table 11- 2 Derating factor of the output current as a function of the line voltage
Article number
Rated output current I
N
at
380 V/400 V
380 V
400 V
415 V
460 V
480 V
6SL3710-1PE32-1_A0 205 A
100 %
100 %
95.9 %
83.5 %
78 %
6SL3710-1PE32-5_A0 245 A
100 %
100 %
95.3 %
81.3 %
75 %
6SL3710-1PE33-0_A0 300 A
100 %
100 %
96.6 %
86.2 %
81.6 %
6SL3710-1PE33-7_A0 370 A
100 %
100 %
96.9 %
87.8 %
83.7 %
6SL3710-1PE34-6_A0 460 A
100 %
100 %
96.4 %
85.4 %
80.6 %
6SL3710-1PE35-8_A0 585 A
100 %
100 %
96.9 %
87.8 %
83.7 %
6SL3710-1PE36-6_A0 655 A
100 %
100 %
96.4 %
85.4 %
80.6 %
6SL3710-1PE37-4_A0 735 A
100 %
100 %
96.6 %
86.6 %
82.1 %
Current derating as a function of the pulse frequency
In the factory setting, the drive starts with a pulse frequency of 4 kHz and reduces
automatically the pulse frequency to the associated required frequencies when loaded.
When the load decreases, the pulse frequency is increased automatically up to 4 kHz.
The values of the rated current apply to a pulse frequency of 2 kHz at 40° C ambient
temperature and are reached at any time by the automatic adaptation of the output pulse
frequency.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......