6.9 Communication over CANopen
Inverter cabinet units
268
Operating Instructions, 12/2014, A5E32923362A
●
Acyclic asynchronous (values: 254, 255)
–
TPDO when a process data has changed in the telegram.
–
The controller accepts the RPDO immediately.
Inhibit time
The inhibit time defines the minimum interval between two transmissions.
Synchronous data transmission
A periodic synchronization object (SYNC object) ensures that the devices on the CANopen
bus remain synchronized during transmission.
Each PDO transferred as synchronization object must include a "transmission type" 1 ... n:
●
Transmission type 1: PDO in each SYNC cycle
●
Transmission type n: PDO in every n-th SYNC cycle
The following diagram shows the principle of synchronous and asynchronous transmission:
Figure 6-25 Principle of synchronous and asynchronous transmission
For synchronous TPDOs, the transmission mode also identifies the transmission rate as a
factor of the SYNC object transmission intervals.
The CAN controller transfers data from synchronous RPDOs that it received after a SYNC
signal only after the next SYNC signal to the inverter.
Note
The SYNC signal synchronizes only the communication on the CANopen bus and not
functions in the inverter, e.g. the clock times of the speed control.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......