Functions
7.4 Setpoint calculation
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
351
7.4.5
Skip frequency bands
The inverter prevents continuous motor operation
at speeds in the suppression-speed range.
This can prevent speeds from being approached
stationary that, for example, cause excitation of
resonancy vibrations of the drive train.
To ensure that the speed does not constantly
increase and decrease in the suppression band-
width (speeds), the bands are assigned a hyste-
resis.
The suppression speeds apply in the positive and
negative direction of rotation.
Table 7- 18 Setting skip frequency bands
Parameter
Description
p1091
Suppression speed 1
p1092
Suppression speed 2
p1093
Suppression speed 3
p1094
Suppression speed 4
p1098
Suppression speed scaling
p1101
Suppression speed bandwidth
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......