Functions
7.7 Application-specific functions
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
403
Application example
To improve the air circulation in the stairwells, the ventilation control creates a slight
underpressure in the building. With this control, a fire would mean that smoke gases enter
into the stairwell. This would then mean that the stairs would be blocked as escape or
evacuation route.
Using the essential service mode function, the ventilation switches over to the control of an
overpressure. This prevents the propagation of smoke in the stairwell, thereby keeping the
stairs free as an evacuation route.
Settings for the essential service mode
Procedure
Proceed as follows in order to be able to use the essential service mode:
1.
Interconnect a free digital input as source for the essential service mode.
Example DI3: Set p3880 = 722.3.
Ensure that this digital input is not interconnected with other functions.
2.
Using p3881, set the setpoint source for the essential service mode
Option 1:
–
P3881 = 0: Last recognized setpoint (factory setting) or
–
p3881 = 1: Fixed setpoint 15, or
–
p3881 = 2: Analog setpoint, or
–
p3881 = 3: Fieldbus
Option 2:
–
p3881 = 4: Technology loop controller
–
Using p3884, set the source for the essential service mode setpoint.
If you cannot connect a setpoint in p3884, then the inverter takes technology setpoint
1 that has been connected (p2253).
3.
Using p3882, set the source for the alternative setpoint.
–
P3882 = 0: Last recognized setpoint (factory setting)
p3882 = 1: Fixed speed setpoint which is defined in p1015
p3882 = 2: Maximum speed (value of p1082)
4.
Parameterize the source to select the direction of rotation for the essential service mode.
Option 1: Emergency setpoint using p3881 = 0, 1, 2, 3:
Using p3883, invert the direction of rotation for the essential service mode. To do this,
interconnect p3883 with a digital input, e.g. with digital input 4 (DI4): Set p3883 = 722.4
The following applies:
–
p3883 = 0 → normal direction of rotation in the essential service
mode,
–
p3883 = 1 → inverted direction of rotation in the essential service mode,
Option 2: Essential service mode via technology controller (p3881 = 4)
If you enter the setpoint for the essential service mode via the technology controller, then
the direction of rotation of the essential service mode setpoint is always valid.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......