Functions
7.7 Application-specific functions
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
411
Parameters to set and activate the cascade control
p0730 = r2379.0
Signal source for digital output 0
Control external motor 1 via DO 0
p0731 = r2379.1
Signal source for digital output 1
Control external motor 2 via DO 1
p0732 = r2379.2
Signal source for digital output 2
Control external motor 3 via DO 2
p2200 = 1
Technology closed-loop controller release
Activate technology closed-loop controller
p2251 = 0
Technology closed-loop controller mode
Technology closed-loop controller as main speed setpoint
p2370 = 1
Cascade control enable
p2371
Cascade control - configuration
Define activation sequence
p2372
Cascade control - motor selection mode
Define automatic motor switch-on
p2373
Cascade control - switch-in threshold
Define switch-on threshold
p2374
Cascade control - switch-in delay
Define delay time
p2375
Cascade control switch-off delay
Define delay time for de-staging
p2376
Cascade control - overcontrol threshold
Define overcontrol threshold
p2377
Cascade control - interlock time
Define interlock time
p2378
Cascade control - connect/disconnect speed
Define the speed for the main drive after connecting/disconnecting a motor
r2379
Cascade control - status word
p2380[0...2]
Cascade control - operating hours
Operating hours of the individual uncontrolled motors
p2381
Cascade control - maximum time for continuous mode
p2382
Cascade control - absolute operating time limit
p2383
Cascade control - switch-off sequence
Define the switch-off sequence for an OFF command
p2384
Cascade control - motor switch-on delay
Define motor switch-on delay
p2385
Cascade control - connect hold time
Define speed hold time after connecting an external motor
p2386
Cascade control - motor switch-off delay
Define motor switch-off delay
p2387
Cascade control - switch-off speed hold time
Define speed hold time after disconnecting an external motor
For more information, refer to the parameter descriptions and the function block diagram
7036 in the List Manual.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......