Technical specifications
11.3 Technical specifications
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
481
Table 11- 5 Type A, 3-phase 380 ... 480 V AC, Part 3
Article number
6SL3710- 1PE36-6AA0
1PE37-4AA0
Rated power
- For I
L
at 50 Hz 400 V
1)
- For I
L
at 60 Hz 460 V
2)
- For I
H
at 50 Hz 400 V
1)
- For I
H
at 60 Hz 460 V
2)
kW
hp
kW
hp
355
450
250
300
400
500
315
350
Output current
- Rated current I
N
(400 V ±10%)
- Rated current I
N
(480 V ±10%)
- Base load current I
L
(400 V ±10%)
3)
- Base load current I
L
(480 V ±10%)
3)
- Base load current I
H
(400 V ±10%)
4)
- Base load current I
H
(480 V ±10%)
4)
A
A
A
A
A
A
655
526
640
515
491
394
735
602
720
590
551
452
Input current
- Rated input current (400 V ±10%)
5
- Rated input current (480 V ±10%)
5
- Base load current I
L
(400 V ±10%)
3)
- Base load current I
L
(480 V ±10%)
3)
- Base load current I
H
(400 V ±10%)
4)
- Base load current I
H
(480 V ±10%)
4)
- Input current, max.
- Power requirement for the 24 V DC
auxiliary supply
A
A
A
A
A
A
A
A
668
536
654
525
501
402
881
1.0
750
614
735
602
562
461
992
1.0
Supply voltages
- Line voltage
- Line frequency
- Electronics power supply
V
ACrms
Hz
V
DC
380 V 3 AC -10 % to 480 V 3 AC +10 % (-15 % < 1 min)
47 to 63 Hz
24 (20.4 to 28.8)
Power loss, for I
N
and 40°C
kW
9.443
9.907
Coolant requirements
m
3
/s
0.6
0.6
Sound pressure level L
pA
(1 m) at 50/60 Hz
dB(A)
69/69
69/69
Line connection
- Recommended: IEC
6)
- maximum: IEC
- Fixing screw
mm
2
mm
2
3 x 185
4 x 240
M12
3 x 185
4 x 240
M12
Motor connection
- Recommended: IEC
6)
- maximum: IEC
- fixing screw
7)
mm
2
mm
2
2 x 240
4 x 240
M12 x 40
2 x 240
4 x 240
M12 x 40
Protective conductor connection
- maximum: IEC
Fixing screw
mm
2
6 x 240
M12
6 x 240
M12
Motor cable length, max.
- compliant with categories C2 and C3
according to EN 61800-3, shielded
m
100
100
- non-compliant with the limit values for
interference and without output choke
or dv/dt filter, unshielded
m
200
200
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......