Commissioning
5.5 Procedure for commissioning via STARTER
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
149
Figure 5-8
Setting the access point
⇒
Select the access point:
●
Select the S7ONLINE access (STEP7), if the connection to the drive unit is established
via PROFINET or PROFIBUS.
●
Select the DEVICE access, if the connection to the drive unit is established via the USB
interface.
⇒
Click on OK, to acknowledge the selection and close the window.
⇒
In the previous window, click on PG/PC ... and set up the interface in accordance with your
device configuration.
The Properties..., Copy..., Delete... and Select... buttons are now active.
Figure 5-9
Setting the interface