Technical specifications
11.3 Technical specifications
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
477
11.3.1
Cabinet unit type A, 3-phase 380 - 480 VAC
Table 11- 3 Type A, 3-phase 380 ... 480 VAC, Part 1
Article number
6SL3710- 1PE32-1AA0
1PE32-5AA0
1PE33-0AA0
Rated power
- For I
L
at 50 Hz 400 V
1)
- For I
L
at 60 Hz 460 V
2)
- For I
H
at 50 Hz 400 V
1)
- For I
H
at 60 Hz 460 V
2)
kW
hp
kW
hp
110
125
90
100
132
150
110
100
160
200
132
150
Output current
- Rated current I
N
(400 V ±10%)
- Rated current I
N
(480 V ±10%)
- Base load current I
L
(400 V ±10%)
3)
- Base load current I
L
(480 V ±10%)
3)
- Base load current I
H
(400 V ±10%)
4)
- Base load current I
H
(480 V ±10%)
4)
A
A
A
A
A
A
205
160
200
156
164
128
245
184
240
180
196
147
300
245
290
240
240
196
Input current
- Rated input current (400 V ±10%)
5
- Rated input current (480 V ±10%)
5
- Base load current I
L
(400 V ±10%)
3)
- Base load current I
L
(480 V ±10%)
3)
- Base load current I
H
(400 V ±10%)
4)
- Base load current I
H
(480 V ±10%)
4)
- Input current, max.
- Power requirement for the 24 V DC
auxiliary supply
A
A
A
A
A
A
A
A
218
171
213
167
175
137
288
1.0
262
197
257
193
210
157
347
1.0
317
262
307
257
254
210
415
1.0
Supply voltages
- Line voltage
- Line frequency
- Electronics power supply
V
ACrms
Hz
V
DC
380 V 3 AC -10 % to 480 V 3 AC +10 % (-15 % < 1 min)
47 to 63 Hz
24 (20.4 to 28.8)
Power loss, for I
N
and 40°C
kW
3.377
3.939
4.543
Coolant requirements
m
3
/s
0.21
0.21
0.21
Sound pressure level L
pA
(1 m) at 50/60 Hz
dB(A)
66/66
66/66
66/66
Line connection
- Recommended: IEC
6)
- maximum: IEC
- Fixing screw
mm
2
mm
2
2 x 70
2 x 240
M12
2 x 95
2 x 240
M12
2 x 120
2 x 240
M12
Motor connection
- Recommended: IEC
6)
- maximum: IEC
- fixing screw
7)
mm
2
mm
2
2 x 50
2 x 240
M12 x 40
2 x 70
2 x 240
M12 x 40
2 x 95
2 x 240
M12 x 40
Protective conductor connection
- maximum: IEC
Fixing screw
mm
2
3 x 240
M12
3 x 240
M12
3 x 240
M12
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......