Operating Instructions, 12/2014, A5E32923362A
If you wish to use the real-time clock, you must set the time and date once when
commissioning. If you restore the inverter factory setting, the real-time clock parameters are
not reset. Summer and winter times must be set manually.
Parameter
Real-time clock (RTC)
p8400[0]
RTC time, hour (0 … 23)
p8400[1]
RTC time, minute (0 … 59)
p8400[2]
RTC time, second (0 … 59)
p8401[0]
RTC date, day (1 … 31)
p8401[1]
RTC date, month (1 … 12)
p8401[2]
RTC date, year (1 … 9999)
r8404
RTC weekday
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
p8405
RTC activate/deactivate alarm A01098
Sets whether the real-time clock issues an alarm if the time is not running in syn-
chronism (e.g. after a longer power supply interruption).
0: Alarm A01098 deactivated
1: Alarm A01098 activated (factory setting)
Accept the real-time clock in the alarm and fault buffer
Using the real-time clock, you can track the sequence of alarms and faults over time. When
an appropriate message occurs, the real-time clock is converted into the UTC time format
(Universal Time Coordinated):
Date, time
⇒ 01.01.1970, 0:00 + d (days) + m (milliseconds)
The number "d" of days and the number "m" of milliseconds is transferred into the alarm and
fault times of the alarm or fault buffer, see Section Alarms, faults and system messages
(Page 433).
Converting UTC into RTC
An RTC can again be calculated from the UTC.
Proceed as follows to calculate a date and time from a fault or alarm time saved in the UTC
format:
1.
Calculate the number of seconds of UTC:
Number of seconds = ms / 1000 + days × 86400
2.
In the Internet, you will find programs to convert from UTC into RTC, e.g.:
UTC to RTC (
http://unixtime-converter.com/
3.
Enter the number of seconds in the corresponding screen and start the calculation.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......