Electrical installation
4.8 Signal connections
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
77
Motor temperature sensor interface
Table 4- 10 Motor temperature sensor interface
Pin
Designation
Technical data
14
T1 MOTOR
Positive input for motor temperature sensor
Type: PTC, KTY sensor, Thermo-Click
15
T2 MOTOR
Negative input for motor temperature sensor
Max. connectable cross-section: 1.5 mm²
Power supply
Table 4- 11 Power supply
Pin
Designation
1)
Technical data
9
+24 V OUT
Power supply output
24 VDC, max. 200 mA
28
GND
Reference potential of the power supply/internal electronics ground
1
+10 V OUT
Power supply output
10 VDC ±0.5 V, max. 10 mA
2
GND
Reference potential of the power supply/internal electronics ground
31
+24 V IN
Power supply input
18 ... 30 VDC, max. 1500 mA
32
GND IN
Reference potential of the power supply input
35
+10 V OUT
Power supply output
10 VDC ±0.5 V, max. 10 mA
36
GND
Reference potential of the power supply/internal electronics ground
Max. connectable cross-section: 1.5 mm²
1)
GND: reference potential
X150 P1/P2 PROFINET interface
Table 4- 12 X150 P1 and X150 P2 PROFINET
Pin
Signal name
Technical data
1
RXP
Receive data +
2
RXN
Receive data -
3
TXP
Transmit data +
4
Reserved, do not use
5
Reserved, do not use
6
TXN
Transmit data -
7
Reserved, do not use
8
Reserved, do not use
Connector type: RJ45 socket
Cable type: PROFINET
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......