Functions
7.7 Application-specific functions
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
381
The DC-braking function is possible only for induction motors.
DC braking when falling below a start speed
Precondition: p1230 = 1 and p1231 = 14
DC braking when a fault occurs
Precondition: Fault number and fault response
are assigned using p2100 and p2101
DC braking initiated using a control command
Precondition: p1231 = 4 and p1230 = control
command, e.g. p1230 = 722.3 (control command
via DI 3)
DC braking when switching off the motor
Precondition: p1231 = 5 or p1230 = 1 and p1231
= 14
DC braking when falling below a starting speed
1.
The motor speed has exceeded the starting speed.
2.
The inverter activates the DC braking as soon as the motor speed falls below the starting
speed.
DC braking when a fault occurs
1.
A fault occurs, which initiates DC braking (DCBRK) as response.
2.
The motor brakes along the down ramp to the speed for the start of DC braking.
3.
DC braking starts.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......