Electrical installation
4.8 Signal connections
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
101
Shield support
The shield connection of shielded control cables on the terminal block -X9 is established in
the immediate vicinity of the terminal block. For this purpose, the mounting plates have
cutout sections which are used to snap the supplied shield springs into place. The shields of
incoming and outgoing cables must be applied directly to these shield connections. It is
important here to establish the greatest possible area of contact and a good conductive
connection.
Note
Shield springs
These shield springs can be used for all control cables in the cabinet unit because all the
shield connections are identical in design.
CAUTION
Danger of injury due to cut injuries occurring when the shield is connected
The sharp edges of the shield springs can cause cut injuries.
•
Use the appropriate personnel protection equipment, e.g. gloves.
X9: Customer terminal block
Terminal
Name
Significance
Input/
output
Technical data
1
P24
Input
24 V DC (20.1 ... 28.8 V)
Current consumption: max. 2 A
2
M24
Input
3
External alarm
Input
Voltage: -3 V to +30 V
Current drain:
6.4 mA at 24 V DC
1.3 mA at <5 V
4 mA at >15 V
8 mA at 30 V
Level (including ripple):
High level: 15 V ... 30 V
Low level: -3 V to +5 V
4
External fault
Input
5
EMERGENCY
OFF
EMERGENCY OFF category
0
Input
6
EMERGENCY
STOP
EMERGENCY STOP cate-
gory 1
Input
7
M24
Input
8
V
DC link
loaded
Enable signal "V
DC link
charged"
Output
Voltage: 24 V DC
Max. load current: 500 mA
Continuously short-circuit proof
The output current is taken from the supply
at X9, terminal 1.
9
NC
Not connected
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......