Operation
6.3 Communication via PROFINET
Inverter cabinet units
180
Operating Instructions, 12/2014, A5E32923362A
Procedure
Proceed as follows to load the GSDML of the inverter:
●
Load the GSDML of the inverter into the PROFINET controller, i.e. into your controller.
You can load the GSDML of your inverter in two ways:
–
You can find the GSDML of the SINAMICS inverter on the Internet
http://support.automation.siemens.com/WW/view/en/22339653/133100
–
The GSDML is saved in the inverter. If you insert the memory card in the inverter and
set p0804 = 12 , the GSDML will be written to the /SIEMENS/SINAMICS/DATA/CFG
folder on the memory card as a compressed file (PNGSD.ZIP).
●
Unpack the GSDML before you use the device file.
6.3.4
Select telegram
The following telegrams are available:
Parameter
Description
p0015
Macro drive unit
Configure the interface in the basic commissioning, and select a telegram.
p0922
PROFIdrive telegram selection
Set the send and receive telegram, also see Cyclic communication (Page 186)
1:
20:
350:
352
353:
354:
999:
Standard telegram 1, PZD-2/2 (factory setting)
Standard telegram 20, PZD-2/6
SIEMENS telegram 350, PZD-4/4
SIEMENS telegram 352, PZD-6/6
SIEMENS telegram 353, PZD-2/2, PKW-4/4
SIEMENS telegram 354, PZD-6/6, PKW-4/4
Free telegram configuring with BICO, see
Extend telegrams and change signal interconnection (Page 192)
Precondition
In the basic commissioning, you have selected a setting with fieldbus.
See also Section: Commissioning (Page 123).
Procedure
Proceed as follows to set a specific telegram in the inverter:
●
Use STARTER or the IOP to set parameter p0922 to the appropriate value.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......