Operation
6.2 Basic information about the drive system
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
175
Table 6- 2
Binectors
Abbreviation and
symbol
Name
Description
Binector input
Binector input
(signal sink)
Can be interconnected to a binector output as
source.
The number of the binector output must be en-
tered as a parameter value.
Binector output
Binector output
(signal source)
Can be used as a source for a binector input.
Connectors, CI: Connector input, CO: Connector output
A connector is a digital signal e.g. in 32–bit format. It can be used to emulate words (16 bits),
double words (32 bits) or analog signals. Connectors are subdivided into connector inputs
(signal sink) and connector outputs (signal source).
The options for interconnecting connectors are restricted to ensure that performance is not
adversely affected.
Table 6- 3
Connectors
Abbreviation and sym-
bol
Name
Description
Connector input
Connector input
(signal sink)
Can be interconnected to a connector output as
source.
The number of the connector output must be en-
tered as a parameter value.
Connector output
Connector output
(signal source)
Can be used as a source for a connector input.
Interconnecting signals using BICO technology
To interconnect two signals, a BICO input parameter (signal sink) must be assigned to the
desired BICO output parameter (signal source).
The following information is required in order to connect a binector/connector input to a
binector/connector output:
•
Binectors:
Parameter number and bit number
•
Connectors with no index: Parameter number
•
Connectors with index:
Parameter number and index
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......