Interrupts/diagnostics alarms
5.1 Status and error displays
DI 8x24VDC 8xM8 (6ES7141-5BF00-0BA0)
Equipment Manual, 08/2021, A5E32349579-AD
19
Meaning of the LEDs
The following tables set out the meaning of the status and error displays. Corrective
measures for diagnostics alarms can be found in the section Diagnostics alarms (Page 20).
DIAG LED
Table 5- 1
Error display of the DIAG LED
DIAG LED
Meaning
Off
No supply voltage 1L+
Flashes
•
Module parameters not assigned
(after switching on the supply voltage 1L+)
•
Loading firmware
(while the firmware update is being performed, all LEDs retain their cur-
rent status)
•
No connection to the ET-Connection and/or the fieldbus
On
Module parameters assigned and no module diagnostics
Flashes
Module parameters assigned and module diagnostics
LED channel status
Table 5- 2
LED channel status display
LED channel status Meaning
Off
Process signal = 0
On
Process signal = 1