OPC UA communication
9.3 Using the S7-1500 as an OPC UA server
Communication
268
Function Manual, 05/2021, A5E03735815-AJ
UDT "LocalizedText"
For the basic data type "LocalizedText", create the following PLC data type:
Figure 9-45 "LocalizedText" UDT
The EncodingByte indicates which fields (Locale or Text) are available:
EncodingByte
Meaning
0
The fields Locale and Text are empty
1
The field Locale has content, the field Text is empty
2
The field Locale is empty, the field Text has content
3
The fields Locale and Text have content
UDT "ByteString"
For the basic data type "ByteString", create the following PLC data type; in this case, for
example, a ByteString array with 12 elements:
Figure 9-46 "ByteString" UDT