Technical specifications
9.3 Transport and storage conditions
IO-Link I/O modules
System Manual, 08/2021, A5E48755395-AB
57
Emission of radio frequency interference
The table below shows the interference emission of electromagnetic fields according to
EN 55011: limit class A, group 1.
Table 9- 4
Interference emission of electromagnetic fields
Frequency
Interference emission
Measuring
distance
30 ... 230 MHz
<40 dB (µV/m) Q
10 m
230 ... 1000 MHz
<47 dB (µV/m) Q
10 m
1 GHz ... 3 GHz
<76 dB (µV/m) P
3 m
3 GHz ... 6 GHz
<80 dB (µV/m) P
3 m
24 V supply connection
The following table shows measurement ranges for low voltage according to EN 55016.
Table 9- 5
Interference emission from the power supply
Frequency
Interference emission
0.15 ... 0.5 MHz
89 dB (µV) Q
76 dB (µV) M
0.5 ... 30 MHz
83 dB (µV) Q
70 dB (µV) M
9.3
Transport and storage conditions
Transport and storage conditions
The ET 200AL IO-Link I/O modules surpass the requirements of IEC 61131-2 regarding
transport and storage conditions. The following table shows the conditions that apply to
modules transported or stored in their original packaging.
Table 9- 6
Transport and storage conditions
Type of condition
Permitted range
Free fall
≤
0.3 m
Temperature
-40 °C ... +70 °C
Temperature variation
20 K/h
Barometric pressure
1140 ... 660 hPa
(corresponds to an altitude of -1000 to 3500 m)
Relative humidity
5 ... 95%
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......