Interrupts/diagnostics alarms
5.3 Diagnostics alarms
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
Equipment Manual, 08/2021, A5E32350124-AG
35
Structure of the additional interrupt information
Table 5- 4
Structure of USI = W#16#0001
Data block name
Contents
Comment
Bytes
USI
(User Structure Identifi-
er)
W#16#0001
Additional interrupt info for hardware inter-
rupts of the I/O module
2
The channel that triggered the hardware interrupt follows.
Channel
B#16#00 to
B#16#03
Number of channel which triggered the event 1
The error event that triggered the hardware interrupt follows.
Event
B#16#03
Low limit 1 violated
1
B#16#04
High limit 1 violated
B#16#05
Low limit 2 violated
B#16#06
High limit 2 violated
5.3
Diagnostics alarms
A diagnostics alarm is output for each diagnostic event and the DIAG LED flashes red on the
analog input module. You can read out the diagnostics alarms, for example, in the
diagnostics buffer of the CPU. You can evaluate the error codes with the user program.
The following tables set out the diagnostics alarms for the set measuring range.
Table 5- 5
Diagnostics alarms - for the measuring range: 1 V to 5 V, 2-DMU 4 mA to 20 mA and
4-DMU 4 mA to 20 mA
Diagnostics
alarm
Error code Meaning
Remedy
Short-circuit
1
H
Short-circuit encoder supply to
ground
Correct interplay between mod-
ule and encoder
Wire break
6
H
Wire break between the module
and sensor
Connect the cable
Channel not connected (open)
•
Deactivate diagnostics
•
Connect the channel
•
Deactivate channel
High limit violat-
ed
7
H
Value is above overrange.
Correct interplay between mod-
ule and sensor
Low limit violat-
ed
8
H
Value is below underrange.
Correct interplay between mod-
ule and sensor
Error
9
H
Value is significantly above or
below underrange/overrange.
Correct interplay between mod-
ule and sensor
Parameter error 10
H
Module parameter assignment is
faulty
Correct the parameter assign-
ment
Hardware inter-
rupt lost
16
H
At least one hardware interrupt
could not be signaled because
too many hardware interrupts are
pending.
Correct the program or the pro-
cess
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......