DIAGInput LEDs
Meaning
On red
Channel fault or module fault affecting the channel
Alternately Flashes
red/green
Fault resolved, awaiting reintegration
Channel LEDs for 1oo2 input channels
Table 6- 5
Meaning of the channel LEDs for 1oo2 input channels
Primary input LED
Secondary input LED Meaning
Off
Off
Process signal = 0 (equivalent)
On green
On green
Process signal = 1 (equivalent)
Off
On green
Process signal = 0 (nonequivalent)
On green
Off
Process signal = 1 (nonequivalent)
On red
On red
Channel fault or module fault affecting the channel
Alternately Flashes
red/green
Alternately Flashes
red/green
Fault resolved, awaiting reintegration
Channel LED for output channels
Table 6- 6
Meaning of the channel LED for output channels
Output LED
Meaning
Off
Process signal = 0 or channel deactivated
On green
Process signal = 1
On red
Channel fault or module fault affecting the channel
Alternately Flashes
red/green
Fault resolved, awaiting reintegration
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......