Configuring
Distributed I/O system
62
System Manual, 08/2021, A5E31861578-AJ
Configuration - PROFIBUS maximum configuration
Each of the connections for ET-Connection occupies a slot in the configuration. The slot for
ET-Connection1 is statically defined in the PROFIBUS GSD file. ET-Connection1 is always
permanently installed in slot 1. Always place the topology module for ET-Connection2 on slot
18. You do not need to fill slots in the configuration for ET-Connection1 with dummy
modules.
The fixed slot assignment of ET-Connection1 and ET-Connetion2 offers you the following
advantages:
•
You can expand ET-Connection1 and ET-Connection2 without a high workload; for
ET-Connection1 you need to remove the placeholder, the I/O module is placeable (no
placeholders are needed for ET-Connection2)
•
You cannot configure more modules on ET-Connection1 or ET-Connection2 than are
allowed.
•
Transparency in configuration control
•
Simplification of diagnostics alarms and troubleshooting
The figure below shows the maximum configuration with modules of the ET 200AL
distributed I/O system.
Figure 6-2
PROFIBUS maximum configuration
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......