Applications of the F-I/O module
5.1 Digital input applications
Digital I/O module F-DI 4+F-DQ 2x24VDC/2A, 4xM12 (6ES7146-5FF00-0BA0)
Equipment Manual, V1.0, 05/2021, A5E51082342-AA
41
Input architectures for achieving Safety Integrity Level (SIL)/Category/Performance Level (PL)
The following are the minimum conditions which must be met for achieving the
corresponding safety requirements:
Table 5- 1
Safety Integrity Level (SIL)/Category/Performance Level (PL) requirements
Application
Sensor
supply
1
Sensor
evaluation
Channel
connection
Type of sensor
connection
Achievable
SIL/Category/PL
Without
short-
circuit
detection
With
short-
circuit
detection
1
Internal
1oo1
evaluation
Single input
1 channel
2/3/d
2
External
3
Internal
1oo2
evaluation
Two inputs
2 channel
equivalent
3/3/e
3/4/e
4
External
3/3/e
5
Internal
2 channel - 3 wire
nonequivalent
3/3/e
3/4/e
6
External
3/3/e
7
Internal
2 channel - 4 wire
nonequivalent
3/3/e
3/4/e
8
External
3/3/e
1
The F-DI 4/F-DQ 2 Fail-Safe module uses M12 I/Oconnections and is intended for use outside a
cabinet in IP67 applications (everything sealed). If you require the use of an external supply, cut the
M12 cable and make the connection inside a sealed cabinet or inside a sealed sensor. For external
supplies, do not connect the pin 1 wire (V
S1
) or the pin 5 wire (V
S2
) in the M12 cable. This action
prevents the sensor supply (which may be ON due to a different channel being configured as inter-
nal) from being shorted to the external 24 V DC. In addition, make the external 24 V DC connection
inside a sealed cabinet or inside a sealed sensor.
Refer to "Pin assignment" (Page 19) for further information on connector pin assignments.
5.1.1
Applications 1 and 2: 1oo1 evaluation of single-channel sensors
F-DI application mode 1
This application mode uses single-channel sensors with a 1oo1 evaluation as shown in the
following illustrations. When you use an internal sensor supply, you can successfully perform
short-circuit detection.
Note
To incorporate F-DI application mode 1 into a SIL 2-rated application, ensure the sensors are
appropriately qualified devices.
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......