Representation of analog values
3.3 Representation of output ranges
Analog value processing
64
Function Manual, 06/2014, A5E03461439-AC
Table 3- 6
Unipolar output ranges
Dec. value Output
value in %
Data word
Range
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
32511
117.589
0 1 1 1 1 1 1 1 x x x x x x x x Maximum output
value*
32511
117.589
0 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 Over range
27649
100.004
0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 1
27648
100.000
0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 0 Rated range
1
0.003617
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
0
0.000
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0
0.000
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Minimum output
value**
* When values > 32511 are specified, the output value is limited to 117.589 % or 0 % (0.0 V / 0.0 mA), depending on the
module used.
** When values < 0 are specified, the output value is limited to 0% (0.0 V / 0.0 mA).