Representation of analog values
B.3 Representation of analog values for resistance-based sensors
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
48
Equipment Manual, 08/2021, A5E32350124-AG
B.3
Representation of analog values for resistance-based sensors
Resistance-based sensor
Table B- 3
Resistance-based sensor of 150
Ω and 300
Ω
Values
Resistance-based sensor range
Range
Dec.
Hex.
150 Ω
300 Ω
32767
7FFF
>176.38
Ω
>352.77
Ω
Overflow
32511
7EFF
176.38 Ω
352.77 Ω
Overrange
27649
6C01
27648
6C00
150 Ω
300 Ω
Nominal range
20736
5100
112.5 Ω
225 Ω
1
1
5.43
mΩ
10.85
mΩ
0
0
0 Ω
0 Ω
-1
:
-4864
FFFF
:
ED00
(negative values are physically impossible)
Underrange
1
-32768
8000
Underflow
1
1
If the sensors are not connected correctly