Diagnostics and maintenance
4.4 Diagnostics via Web server
PROFINET with STEP 7
Function Manual, 05/2021, A5E03444486-AL
89
Meaning of the colored connections in the set/actual topology:
Table 4- 2
Meaning of the colored connections in the set/actual topology:
Connection
Meaning
Set topology
Actual topology
green
The current actual connection matches the configured set
connection.
detected connections
red
The current actual connection does not match the config-
ured set connection (e.g., port interchanged).
-
yellow
The connection cannot be diagnosed. Causes:
•
The communication to an IO device has been disrupted
(e.g., cable removed)
•
Connection to a passive component
•
Connection to PROFINET devices of another IO controller
or PROFINET system
-
①
Configured and accessible PROFINET devices
Configured and accessible PROFINET devices are displayed dark-gray. Connections show the
ports through which the PROFINET devices of a station are connected.
①
Configured but not accessible PROFINET devices
The configured but not accessible PROFINET devices are displayed in pink with red border
(e.g., device has failed, cable disconnected).
③
Disabled devices
All disabled, configured PROFINET devices are displayed light-gray.
④
Interchanged ports
Interchanged ports are marked red in the set topology view. The currently connected ports
are displayed in the actual topology, the configured set connection in the set topology.
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......