Interrupts/diagnostics alarms
5.3 Diagnostics alarms
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
Equipment Manual, 08/2021, A5E32350124-AG
37
Table 5- 8
Diagnostics alarms - for the measuring range: Pt100 and Ni100
Diagnostics
alarm
Error code Meaning
Remedy
Wire break
6
H
Impedance of encoder circuit too
high
Use a different encoder type or
modify the wiring, for example,
using cables with larger cross-
section
Wire break between the module
and sensor
Connect the cable
Channel not connected (open)
•
Deactivate diagnostics
•
Connect the channel
•
Deactivate channel
High limit violat-
ed
7
H
Value is above overrange.
Correct interplay between mod-
ule and sensor
Low limit violat-
ed
8
H
Value is below underrange.
Correct interplay between mod-
ule and sensor
Parameter error 10
H
Module parameter assignment is
faulty
Correct the parameter assign-
ment
Hardware inter-
rupt lost
16
H
At least one hardware interrupt
could not be signaled because
too many hardware interrupts are
pending.
Correct the program or the pro-
cess
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......