Applications of the F-I/O module
5.3 Examples of application modes for the F-DI 4/F-DQ 2 Fail-Safe module
Digital I/O module F-DI 4+F-DQ 2x24VDC/2A, 4xM12 (6ES7146-5FF00-0BA0)
Equipment Manual, V1.0, 05/2021, A5E51082342-AA
57
Safety doors (1oo1 or 1oo2 evaluation)
For the Safety Doors, you can do one of the following:
•
Use F-DI application mode 1 with the fail-safe Y cable (6ES7194-6KB00-0XA0) to connect
two single-channel sensors with 1oo1 evaluation to one input connection of the F-DI
4/F-DQ 2 Fail-Safe module.
•
Use F-DI application mode 3 (1oo2 evaluation), using two single-channel sensors on the
same safety door.
Alternatively, use F-DI application mode 5 with the fail-safe Y cable (6ES7194-6KA00-0XA0)
to connect two nonequivalent single-channel sensors with 1oo2 evaluation on the same
safety door.
Safety position switch with interlock (1oo2 evaluation)
Use F-DI application mode 3 and F-DQ application mode 1 to connect the safety position
switch with interlock to the F-DI 4/F-DQ 2 Fail-Safe module.