Functions
5.8 Direct data exchange
PROFINET with STEP 7
Function Manual, 05/2021, A5E03444486-AL
237
5.8.3
Configuring direct data exchange between multiple IO controllers
The procedure for configuring direct data exchange between multiple S7-1500 CPUs is
described below.
First, you set up the communication relations for direct data exchange. You then configure
transfer areas for the communication relations.
Requirements
•
STEP 7 V16 or higher
•
S7-1500 CPUs firmware version V2.8 or higher
•
IRT is configured:
–
All CPUs are in one sync domain.
–
One CPU is the sync master, and the other CPUs are sync slaves.
–
Ports are interconnected.
Setting up the communication relations for direct data exchange
To set up the connection for direct data exchange between multiple S7-1500 CPUs, follow
these steps:
1.
Select the PROFINET interface X1 of the sending CPU.
2.
Change to the table view of the network view, "I/O communication" tab.
The PROFINET interface X1 of the CPU is shown in the "Partner 1" column.
3.
In the "Partner 2" column at "<Drop or select the device here>", select the PROFINET
interface of the communication partner from the drop-down list as the connection partner.
Note the transfer direction:
–
←
: Connection partner is sender
–
→
: Connection partner is receiver
The connection for direct data exchange between the two S7-1500 CPUs is set up.
4.
Repeat step 3 for every other receiving IO controller.
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......