Analog output module AQ 4xU/I 4xM12 (6ES7145-5ND00-0BA0)
Equipment Manual, 08/2021, A5E38687953-AC
33
Representation of analog values
B
This appendix shows the analog values for all output ranges supported by the
AQ 4xU/I 4xM12 analog output module.
Measured value resolution
The digitized analog value is the same for all output values at the same nominal range.
Analog values are output as fixed point numbers in two's complement.
Table B- 1
Resolution of the analog values
Resolution in bits
including sign
Values
Analog value
Decimal
Hexadecimal
High byte
Low byte
16
1
1
H
Sign 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
B.1
Representation of analog values in the voltage output ranges
The tables below list the decimal and hexadecimal values (codes) of the possible voltage
output ranges.
Table B- 2
Voltage output range +/-10 V
Values
Voltage output
range
Range
Dec.
Hex.
±10 V
118.5149%
32767
7FFF
11.76 V
Maximum output value
32512
7F00
117.589%
32511
7EFF
11.76 V
Overrange
27649
6C01
100%
27648
6C00
10 V
Nominal range
75%
20736
5100
7.5 V
0.003617%
1
1
361.7 µV
0%
0
0
0 V
-1
FFFF
-361.7 µV
-75%
-20736
AF00
-7.5 V
-100%
-27648
9400
-10 V
-27649
93FF
Underrange
-117.593%
-32512
8100
-11.76 V
-32513
80FF
-11.76
Minimum output value
-118.519%
-32768
8000
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......