Functions
5.5 Intelligent DP slaves (I-slaves)
PROFIBUS with STEP 7 V13
Function Manual, 12/2014, A5E03775446-AC
89
5.5.6
Diagnostics and interrupt behavior
Diagnostics and interrupt behavior
S7 CPUs have numerous diagnostics and interrupt functions that can, for example, report
errors/faults or failures of underlying DP systems. These diagnostics alarms reduce
downtimes and simplify localization and elimination of problems.
Diagnostics options in the higher-level DP master and in the I-slave
The following diagnostics mechanisms are available to the higher-level DP master and the
I-slave:
●
OB 82 (diagnostic interrupt)
When the I-slave changes mode, the DP master calls OB 82 (diagnostic interrupt).
When the DP master changes mode, the I-slave calls OB 82 (diagnostic interrupt).
●
OB 86 (rack failure)
If the bus connection to the I-slave is interrupted, the DP master calls OB 86
(rack failure).
If the bus connection to the DP master is interrupted, the I-slave calls OB 86
(rack failure).
●
OB 122 (I/O access error)
If you have not set the attribute "Handle errors within block" for OB 122, the following
applies:
–
If the bus connection to the I-slave is interrupted, the DP master calls OB 122
(I/O access error) if there is direct access to the relevant transfer areas.
–
If the bus connection to the DP master is interrupted, the I-slave calls OB 122
(I/O access error) if there is direct access to the relevant transfer areas.
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......