Interrupts, error messages, diagnostics and system alarms
5.1 Status and error displays
IM 157-1 PN (6ES7157-1AB00-0AB0)
28
Equipment Manual, 05/2021, A5E32347036-AE
Meaning of the LEDs
The following tables set out the meaning of the status and error displays. Corrective
measures for diagnostics alarms can be found in the section Diagnostics alarms (Page 32).
LED RUN, LED ERROR, LED MAINT
Table 5- 1
Status and error displays of the LEDs RUN, ERROR, MAINT
LEDs
Meaning
Solution
RUN
ERROR
MAINT
Off
Off
Off
Missing or insufficient supply voltage on
interface module.
Check the supply voltage or switch it on
on the interface module.
On
On
On
Test of LEDs during startup: The three
LEDs light up simultaneously for approxi-
mately 0.25 s.
---
Flashes
Off
Off
Interface module is deactivated.
Activate the interface module with the
configuration software or the user pro-
gram.
Interface module is not configured.
Configure the interface module with the
configuration software.
ET 200AL starts up.
---
ET 200AL is being assigned parameters.
On
Not rele-
vant
Not rele-
vant
ET 200AL is currently exchanging data
with the IO controller.
---
Not rele-
vant
Flashes
Not rele-
vant
Group error
Evaluate the diagnostics and eliminate the
error.
The preset configuration does not corre-
spond to the actual configuration of the
ET 200AL.
Check the configuration of the ET 200AL
to see whether a module is missing, de-
fective or if a module that is not config-
ured is connected to ET-CON1 or ET-CON2
.
Parameter assignment error in the I/O
module
Evaluate the display of the module status
in STEP 7 or in STEP 7 (TIA portal) and
correct the errors in the I/O module.
Not rele-
vant
Not rele-
vant
On
Maintenance
See section Maintenance events (Page 33)
Flashes
Flashes
Flashes
The "Node flash test" is run (the LEDs
P1 LINK and P2 LINK of the PROFINET
interface also flash).
---
Hardware or firmware defective (The LEDs
P1 LINK and P2 LINK of the PROFINET
interface do not flash).
Replace the interface module.
Flashes
Not rele-
vant
Not rele-
vant
Firmware is loading
(all LEDs remain in their current state
while the firmware update is being writ-
ten)
---
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......