Functions
5.8 Direct data exchange
PROFINET with STEP 7
Function Manual, 05/2021, A5E03444486-AL
235
Configuring transfer areas for direct data exchange
To configure a transfer area for direct data exchange, follow these steps:
1.
Select the communication relation for direct data exchange.
Figure 5-81 Communication relation for direct data exchange
2.
Navigate to the properties of the communication relation to "General" > "Direct data
exchange" > "Transfer areas".
3.
Create a new transfer area by double-clicking on "<Add new>". Assign a meaningful name
for the transfer area.
A transfer area for direct data exchange is created.
Figure 5-82 Transfer area for direct data exchange
The communication direction of the transfer area is specified by the communication relation.
You cannot change the communication direction of the transfer area.