Cable shielding
4.3 Connecting the cable shielding for ET 200AL
Designing interference-free controllers
20
Function Manual, 06/2014, A5E03461486-AB
4.3
Connecting the cable shielding for ET 200AL
Each module of the ET 200AL distributed I/O system features a functional ground
connection.
Use only shielded cables for connection of analog signals, PROFINET and PROFIBUS
signals and for the ET-Connection. If you have screwed the plug in correctly, the interference
currents that occur are diverted to the metal parts and functional ground.
If you attach an ET 200AL module to a conductive, grounded base, the lower mounting bolt
establishes a conductive connection to the earth potential.
If you attach an ET 200AL module to a non-conductive base, connect the lower mounting
bolt to the ground wire at the same time.
The following figure shows how to connect the functional ground via a ground wire, using the
IM 157-1 PN interface module as an example.
Figure 4-4
Connect functional ground via a ground wire
Additional information
You can find more information on installing ET 200AL modules in the Installing Modules
section of the system manual Distributed I/O System ET 200AL
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......