Counting
4.2 Configuration method 4xCount
Digital input/Digital output module DIQ 16x24VDC/0.5A 8xM12 (6ES7143-5AH00-0BA0)
70
Equipment Manual, 08/2021, A5E38688112-AD
4.2.3.3
Diagnostics alarms
For each diagnostic event, a diagnostics alarm is issued and the LED DIAG flashes red on the
digital input/digital output module.
You can read out the diagnostics alarms, for example, from the diagnostics buffer of the CPU.
You can evaluate the error codes with the user program.
Table 4- 29 Diagnostics alarms, their meanings and corrective measures
Diagnostics alarm Error code Meaning
Solution
Short circuit
1
1
H
Short-circuit of an encoder sup-
ply to ground
•
Eliminate the short-circuit
Short-circuit of an output to
ground
Parameter as-
signment error
10
H
Module parameter assignment is
faulty
Correction of the parameter
assignment
Load voltage 2L+
missing
2
11
H
Load voltage 2L+ missing or too
low
•
Check the supply voltage
•
Check the module
Hardware inter-
rupt lost
16
H
At least one hardware interrupt
could not be signaled because
too many hardware interrupts
are pending.
Correct the program or the pro-
cess
1
If a short-circuit of the encoder supply to ground is detected, the diagnostic alarm "Short-circuit" is
always output. This alarm is output even if all channels are configured as outputs.
2
If you are using ET 200AL modules in connection with the ET 200SP distributed I/O system, the diag-
nostic alarm "Load voltage missing" is displayed.
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......