Diagnostics and maintenance
4.9 Maintenance
PROFINET with STEP 7
110
Function Manual, 05/2021, A5E03444486-AL
Example AM_Location slot-oriented
A rack and the terminal blocks located on it each supply AM data. The slot assignments are
shown in the figure.
Figure 4-17 Example of assets with slot-oriented AM_Location coding.
Code the AM_Location as an asset for each module as follows:
Bit 0 – 7: AM_Location.Structure = 0x02 (coding "Slot and SubslotNumber format")
Bit 8 – 15: AM_Location.Reserved1 = 0x00 (padding byte)
Bit 16 – 31: AM_Location.BeginSlotNumber = 2 (the "Rack" asset begins from Slot 2 on)
Bit 32 – 47: AM_Location.BeginSubslotNumber = 0xFFFF (the asset encompasses all the
subslots of Slot 2. Otherwise you specify the no. of the subslot at which the asset begins)
Bit 48 – 63: AM_Location.EndSlotNumber = 4 (the asset ends at Slot 4)
Bit 64 – 79: AM_Location.EndSubslotNumber = 0xFFFF (the asset encompasses all the
subslots of Slot 4. Otherwise you specify the no. of the subslot at which the asset ends)
Bit 80 – 95: AM_Location.Reserved2 = 0x0000 (padding byte)
Bit 96 – 111: AM_Location.Reserved3 = 0x0000
Bit 112 – 127: AM_Location.Reserved4 = 0x0000
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......