Interrupts/diagnostic messages/diagnostics
6.5 Fault types, causes, and corrective measures
Digital I/O module F-DI 4+F-DQ 2x24VDC/2A, 4xM12 (6ES7146-5FF00-0BA0)
72
Equipment Manual, V1.0, 05/2021, A5E51082342-AA
Event ID
Diagnostic
message
F-DI 4/F-DQ 2
Fail-Safe
module
Description
Possible causes
Corrective measures
1
16x0040 Mismatch of safe-
ty destination
address
(F_Dest_Add)
Module
The PROFIsafe driver
has detected a destina-
tion address mismatch.
Checked after new
parameters received.
•
eCoding plug has
been replaced with
a different plug
•
eCoding plug is
defective
•
Incorrect F-source
address was down-
loaded as part of
hardware configu-
ration
•
Reassign the
PROFIsafe F ad-
dresses using STEP
7 (TIA Portal)
•
Replace the eCod-
ing plug
•
Correct the
F-destination ad-
dress in hardware
configuration and
re-download
16x0041 Safety destination
address not valid
(F_Dest_Add)
Module
The PROFIsafe driver
has detected an invalid
destination address.
Checked after new
parameters received.
•
eCoding plug has
been replaced with
a different plug
•
eCoding plug is
defective
•
Reassign the
PROFIsafe F ad-
dresses using STEP
7 (TIA Portal)
•
Replace the eCod-
ing plug
16x0042 Safety source
address not valid
(F_Source_Add)
Module
The PROFIsafe driver
has detected a source
address mismatch or
an invalid source ad-
dress.
Checked after new
parameters received.
•
eCoding plug has
been replaced with
a different plug
•
eCoding plug is
defective
•
Incorrect F-source
address was down-
loaded as part of
hardware configu-
ration
•
Reassign the
PROFIsafe F ad-
dresses using STEP
7 (TIA Portal)
•
Replace the eCod-
ing plug
•
Correct the F-
source address in
hardware configu-
ration and re-
download
16x004B Inconsistent iPa-
rameters (iParCRC
error)
Module
The firmware of the F-
module has detected a
CRC error.
•
Communication
between the F-CPU
and F-module is
disturbed
•
Impermissibly high
electromagnetic in-
terference is pre-
sent
•
Check PROFINET
communications
between the F-
module and F-CPU
•
Eliminate the elec-
tromagnetic inter-
ference
•
Power switched
OFF and ON for
station
•
Reassign the
PROFIsafe F ad-
dresses using STEP
7 (TIA Portal)
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......