IO-Link digital input/digital output module DIQ 4+DQ 4x24VDC/0,5A 8xM8 (6ES7143-5BF00-0BL0)
Equipment Manual, 08/2021, A5E47925743-AB
15
Parameters/address space
4
4.1
Parameters
The following table shows the parameters for the DIQ 4+DQ 4x24VDC/0,5A 8xM8 IO-Link
digital input / digital output module.
Table 4- 1
Parameters
Parameters
Value range
Default
Scope
ISDU index
(decimal)
ISDU sub-
index
(decimal)
Value
Dec
.
Hex
.
Diagnostics: Missing load volt-
age 2L+
Disable
0
0
Disable
Module
131
1
Enable
255 FF
Diagnostics: Short-circuit to
ground
Disable
0
0
Disable
Module
(Short-circuit of
encoder supply
or
of the output to
ground)
131
2
Enable
255 FF
Freely assignable channel 0 … 3 DI
0
0
DI
Channel
131
3 … 6
DQ
255 FF
Reaction to CPU/master STOP
Shutdown
0
0
Shutdown Module
(digital outputs)
131
7
Keep last value 2
2
Output substi-
tute value
3
3
Substitute value channel
0
0
0
0
Channel
(digital outputs)
131
8 ... 15
1
255 FF
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......