Chapter 3: Installation and Configuration
29
Cascading the PX via USB
You can use USB cables to cascade up to eight Raritan devices. All
devices in the USB-cascading chain share the Ethernet connectivity.
Different Raritan models can be cascaded as long as they are running an
appropriate firmware.
The first device in the chain is the master device and all the other are
slave devices. All devices in the chain are accessible over the network,
with the bridging or port-forwarding cascading mode activated on the
master device. See
Setting the Cascading Mode
(on page 136).
Only the master device is connected to the LAN. The LAN connection
method varies based on the cascading mode.
The bridging mode supports the
wired
networking only.
The port forwarding mode supports both the
wired
and
wireless
networking.
For more information on the USB-cascading configuration, see the
USB-Cascading Solution Guide
, which is available from Raritan
website's
Support page
To cascade the PX devices via USB:
1. Verify that the PDUs to be cascaded are running the following
firmware versions by choosing Maintenance > Device Information. If
not, upgrade these devices. See
Updating the PX Firmware
(on
PX2 series: version 2.3.1 or later
PX3 series: version 2.5.10 or later
Note: Port forwarding mode over wireless LAN is supported as of
release 3.1.0. You must upgrade all devices in the chain to version
3.1.0 or higher if wireless networking is preferred.
2. Select one of the devices as the master device.
When the port forwarding mode over wireless LAN is intended,
the master device must be a Raritan product with two USB-A
ports, such as PX3, EMX2-888, PX3TS or BCM2.
3. Connect the master device to the LAN via:
A standard network patch cable (CAT5e or higher) if the bridging
mode is intended.
A standard network patch cable or a Raritan USB WIFI wireless
LAN adapter if the port forwarding mode is intended.
For information on the Raritan USB WIFI adapter, see
USB
Wireless LAN Adapters
(on page 21).
Содержание PX2-1000 SERIES
Страница 5: ......
Страница 71: ...Chapter 4 Connecting External Equipment Optional 52...
Страница 231: ...Chapter 6 Using the Web Interface 212 8 Click OK...
Страница 570: ...Appendix G LDAP Configuration Illustration 551 5 Click OK The PX_Admin role is created 6 Click Close to quit the dialog...
Страница 589: ...Appendix I RADIUS Configuration Illustration 570 Note If your PX uses PAP then select PAP...
Страница 590: ...Appendix I RADIUS Configuration Illustration 571 10 Select Standard to the left of the dialog and then click Add...
Страница 591: ...Appendix I RADIUS Configuration Illustration 572 11 Select Filter Id from the list of attributes and click Add...
Страница 594: ...Appendix I RADIUS Configuration Illustration 575 14 The new attribute is added Click OK...
Страница 595: ...Appendix I RADIUS Configuration Illustration 576 15 Click Next to continue...
Страница 627: ...Appendix K Integration 608 3 Click OK...
Страница 647: ...Index 629 Z Zero U Connection Ports 74 Zero U Products 2...