Chapter 6: Using the Web Interface
259
Sample Environmental-Sensor-Level Event Rule
This section applies to outlet-switching capable models only.
In this example, we want PX to enable the load shedding function when
a contact closure sensor enters the alarmed state. This sample event
rule requires creating a new action before creating the rule.
Step 1: create a new action for enabling the load shedding
mode
1. Choose Device Settings > Event Rules. The Event Rule Settings
dialog appears.
2. Click the Actions tab.
3. Click New Action.
4. In the Action Name field, type a name to identify this action. In this
illustration, type Activate Load Shedding.
5. In the Action field, select "Change load shedding state."
6. In the Operation field, select Start Load Shedding.
7. Click Save to save this action.
After the new action for enabling the load shedding mode is created, you
can create an event rule that can trigger the load shedding mode when
the contact closure sensor enters the alarmed state. This sample event
rule looks like this:
Event: Peripheral Device Slot > Slot 1 > State Sensor >
Alarmed/Open/On
Trigger condition: Alarmed/Open/On
Actions: Activate Load Shedding
Step 2: create the contact closure triggered load shedding event
rule
1. Click the Rules tab.
2. Click
New
Rule.
3. In the "Rule name" field, type a name to identify this event rule. In
this illustration, type Contact Closure Triggered Load Shedding.
4. Select the Enabled checkbox. Otherwise, the new event rule will not
be carried out.
5. Select Events > Peripheral Device Slot to indicate we are specifying
an event related to the environmental sensor.
6. Select the ID number of the desired contact closure sensor. In this
illustration, the ID number of the desired contact closure sensor is 1,
so select Slot 1 in the submenu.
Содержание PX2-1000 SERIES
Страница 5: ......
Страница 71: ...Chapter 4 Connecting External Equipment Optional 52...
Страница 231: ...Chapter 6 Using the Web Interface 212 8 Click OK...
Страница 570: ...Appendix G LDAP Configuration Illustration 551 5 Click OK The PX_Admin role is created 6 Click Close to quit the dialog...
Страница 589: ...Appendix I RADIUS Configuration Illustration 570 Note If your PX uses PAP then select PAP...
Страница 590: ...Appendix I RADIUS Configuration Illustration 571 10 Select Standard to the left of the dialog and then click Add...
Страница 591: ...Appendix I RADIUS Configuration Illustration 572 11 Select Filter Id from the list of attributes and click Add...
Страница 594: ...Appendix I RADIUS Configuration Illustration 575 14 The new attribute is added Click OK...
Страница 595: ...Appendix I RADIUS Configuration Illustration 576 15 Click Next to continue...
Страница 627: ...Appendix K Integration 608 3 Click OK...
Страница 647: ...Index 629 Z Zero U Connection Ports 74 Zero U Products 2...