Chapter 8: Using the Command Line Interface
373
Setting the Outlet Power-On Sequence
This section applies to outlet-switching capable models only.
This command sets the outlet power-on sequence when the PDU powers
up.
config:#
pdu outletSequence <option>
Variables:
<option> is one of the options:
default
, or a comma-separated list of
outlet numbers.
Option
Description
default
All outlets are switched ON in the ASCENDING
order (from outlet 1 to the final outlet) when the
PX device powers up.
A comma-
separated list of
outlet numbers
All outlets are switched ON in the order you
specify using the comma-separated list.
The list must include all outlets on the PDU.
Setting the Outlet Power-On Sequence Delay
This section applies to outlet-switching capable models only.
This command sets the delays (in seconds) for outlets when turning on
all outlets in sequence.
Содержание PX2-1000 SERIES
Страница 5: ......
Страница 71: ...Chapter 4 Connecting External Equipment Optional 52...
Страница 231: ...Chapter 6 Using the Web Interface 212 8 Click OK...
Страница 570: ...Appendix G LDAP Configuration Illustration 551 5 Click OK The PX_Admin role is created 6 Click Close to quit the dialog...
Страница 589: ...Appendix I RADIUS Configuration Illustration 570 Note If your PX uses PAP then select PAP...
Страница 590: ...Appendix I RADIUS Configuration Illustration 571 10 Select Standard to the left of the dialog and then click Add...
Страница 591: ...Appendix I RADIUS Configuration Illustration 572 11 Select Filter Id from the list of attributes and click Add...
Страница 594: ...Appendix I RADIUS Configuration Illustration 575 14 The new attribute is added Click OK...
Страница 595: ...Appendix I RADIUS Configuration Illustration 576 15 Click Next to continue...
Страница 627: ...Appendix K Integration 608 3 Click OK...
Страница 647: ...Index 629 Z Zero U Connection Ports 74 Zero U Products 2...