Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
91
25.9
Disable or re-enable outputs for routing
equipment (H2/B9)
Disabled outputs are listed in menu H4/U1.
Outputs for routing equipment (fire brigade tx / fault tx) can be
disabled and re-enabled via this menu. Disabled output will stay
disabled, until re-enabled again via this menu. Can be useful during
an installation and test period, when only local alarms are required.
Disabled output is indicated by LEDs "Disablements" (L8) and "
Fault
/
Disablements
Fire brigade tx" (L15).
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 78.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B9
Disable or re-enable outputs for
routing equipment ACCEPT? B9
"A"
Routing equipment for FIRE:1, FAULT:1
(1=enabled, 0=disabled) ACCEPT?
To move the cursor, press
"
". Edit and/or press "A"
to accept.
"A"
Disable or re-enable outputs for
routing equipment ACCEPT? B9
Scroll or press "Return" to
return to H2. Scroll or
press "Return" to log off.
Содержание MEW01091
Страница 2: ...This page has deliberately been left blank ...
Страница 141: ...This page has deliberately been left blank ...