EBL128 Operating Instructions V1.1.x
124
What happens by reset of the fire alarm(s) is depending on:
a) if you still are in menu H8/S5 and single encapsulated reset is used
b) if you still are in menu H8/S5 and multiple reset is used
or
if you are logged out (by
pressing "Return" two times
or
automatically after 10 minutes).
Alternative a)
"Reset"
Activate address in alarm mode
ACCEPT? S5
Scroll or press "Return" to
menu H8. Scroll or press
"Return" to log off.
Alternative b)
"Reset"
(Blank)
NOTE!
Multiple reset is default.
100
By Single encapsulated reset each point has to be reset individually.
See also chapter "Alarm reset", page 50.
100
Alarm reset is selected via Win128, "Control Unit Properties", tab
"Advanced".