Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
73
2.
Select "Port" (on the PC) and baud rate. (If the coming download
is not successful, it might depend on to high baud rate.)
3.
SET EBL128 IN
BOOT MODE
. On the c.i.e. main board, up to
the left, is a jumper "JP2" (BOOT) situated. Short jumper "JP2".
Restart
72
EBL128 by disconnecting the mains
and
the battery and
connect them again. The buzzer sounds continuously.
4.
Start the download, i.e. click "Start" in the dialog box.
The buzzer will be turned off. The download status is
indicated in the progress bar. LED "Operation" (L6)
will be turned off. LED "General fault" (L7) is
indicating that EBL128 is in the so called "Boot mode".
LEDs "Alarms queued" (L2) are indicating the Flash
memory programming.
5.
To the left of the progress bar is a "% indicator". It has to show
100 % when the download is ready. (If not, lower the "Baud rate"
and make a new download.)
6.
Open jumper "JP2" (BOOT). Restart EBL128. Close the dialog
box. Regarding the restart, see also chapter "Restart", page 74.
7.
LED "Operation" (L6) will be turned on and LED "General fault"
(L7) and LEDs "Alarms queued" (L2) will be turned off.
21.3
Earlier S/W version download
For some reason it might by required to "downgrade" to an earlier
S/W version. The download procedure is the same as for a new S/W.
21.4
S/W download in Display Units
New S/W for the 1728, 1735 / 1736 & 1826 / 1828 units can also be
downloaded via Win128. The PC has to be connected to the RS232
connector "J2" in the unit respectively.
See the Win128 help chapter (help topic) "Display unit menu" and the
"
Technical Description
" for the unit respectively.
72
As an alternative a restart can be done by momentarily short the two solder
pads marked "JP1" (RESET) – placed close to jumper "JP2".
Содержание MEW01091
Страница 2: ...This page has deliberately been left blank ...
Страница 141: ...This page has deliberately been left blank ...